Voltage Drop Calculations

To Find Volts Lost:

  1. Multiply current (amperes) by the distance (feet in one conductor) by the figure in the table below for the type of system and wire used.
  2. Place a decimal in front of the last six figures.
  3. The result is the number of volts lost.

Note: For AC 3 Phase Current Voltage Drop obtained is phase-to-phase.

Wire Size Power Factor % AC Single Phase AC Three Phase DC
14 AWG

100

90

80

70

60

5880

5360

4790

4230

3650

5090

4640

4150

3660

3160

5880
12 AWG

100

90

80

70

60

3690

3380

3030

2680

2320

3190

2930

2620

2320

2010

3690
10 AWG

100

90

80

70

60

2320

2150

1935

1718

1497

2010

1861

1675

1487

1296

2820
8 AWG

100

90

80

70

60

1462

1373

1248

1117

981

1265

1189

1081

969

849

1462
6 AWG

100

90

80

70

60

918

882

812

734

653

795

764

703

636

565

918
4 AWG

100

90

80

70

60

578

571

533

489

440

501

494

462

423

381

578
2 AWG

100

90

80

70

60

367

379

361

337

309

318

328

313

292

268

363
1 AWG 100

90

80

70

60

291

311

299

284

264

252

269

259

246

229

288
1/0 AWG

100

90

80

70

60

233

257

252

241

227

202

222

218

209

106

229
2/0 AWG

100

90

80

70

60

187

213

212

206

193

162

184

183

178

169

181
3/0 AWG

100

90

80

70

60

149

179

181

177

171

129

155

156

153

148

144
4/0 AWG

100

90

80

70

60

121

152

156

155

151

104

131

135

134

131

114
250 kcmil

100

90

80

70

60

102

136

143

143

141

89

117

123

124

122

97
300 kcmil

100

90

80

70

60

86

121

128

131

130

75

104

111

113

113

81
350 kcmil

100

90

80

70

60

74

109

118

122

122

64

95

102

105

106

69
400 kcmil

100

90

80

70

60

66

101

111

115

116

57

88

96

99

101

60
500 kcmil

100

90

80

70

60

54

89

99

105

108

47

78

86

91

93

48
600 kcmil 100

90

80

70

60

47

83

93

99

103

41

72

81

86

89

40
750 kcmil

100

90

80

70

60

39

75

86

93

97

34

65

75

81

84

32
1000 kcmil 100

90

80

70

60

31

67

79

86

91

27

58

68

75

78

24

To learn more about voltage drop, read Voltage Drop: Picking the Right Cable for the Long Run.

Need a Quote?

Our quick quote form is an easy way to get you the information you need to keep your project on track.

If you still have questions, chat with us online or call us at 800.633.6339. Our customer service representatives are available to answer questions Monday through Friday, 8am - 5pm CST.

Start Your Quote

Customer Portal | Online Account Management Tool for Current Customers     Log In

Copyright © 2013-2017 Magento, Inc. All rights reserved.