National Electrical CodeĀ® Allowable Copper Conductor Ampacities
Ampacity Chart
From the 2017 Edition of the National Electrical CodeĀ® (NEC) NFPA70Ā®
Table 310.15(B)(16)
Table 310.15(B)(17)
Table 310.15(B)(3)(a)
Table 310.15(B)(2)(a)
Need More Help?
Do you have more questions about ampacity or can't find what you are looking for? Contact us! Use the button below to get in touch with one of our wire and cable experts.

Table 310.15(B)(16)
(formerly Table 310.16)
Allowable ampacities of insulated copper conductors rated up to and including 2000 Volts, 60°C through 90°C (140°F through 194°F), Not more than three current-carrying conductors in raceway, cable, or earth (directly buried), based on ambient temperature of 30°C (86°F).

Size | Temperature Rating of Copper Conductor | ||
---|---|---|---|
(AWG or kcmil) | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) |
18 AWG | ā | ā | 14 |
16 AWG | ā | ā | 18 |
14 AWG* | 20 | 25 | |
12 AWG* | 25 | 30 | |
10 AWG* | 30 | 35 | 40 |
8 AWG | 40 | 50 | 55 |
6 AWG | 55 | 65 | 75 |
4 AWG | 70 | 85 | 95 |
3 AWG | 85 | 100 | 115 |
2 AWG | 95 | 115 | 130 |
1 AWG | 110 | 130 | 145 |
1/0 AWG | 125 | 150 | 170 |
2/0 AWG | 145 | 175 | 195 |
3/0 AWG | 165 | 200 | 225 |
4/0 AWG | 195 | 230 | 260 |
250 KCMIL | 215 | 255 | 290 |
300 KCMIL | 240 | 285 | 320 |
350 KCMIL | 260 | 310 | 350 |
400 KCMIL | 280 | 335 | 380 |
500 KCMIL | 320 | 380 | 430 |
600 KCMIL | 350 | 420 | 475 |
700 KCMIL | 385 | 460 | 520 |
750 KCMIL | 400 | 475 | 535 |
800 KCMIL | 410 | 490 | 555 |
900 KCMIL | 435 | 520 | 585 |
1000 KCMIL | 455 | 545 | 615 |
1250 KCMIL | 495 | 590 | 665 |
1500 KCMIL | 525 | 625 | 705 |
1750 KCMIL | 545 | 650 | 735 |
2000 KCMIL | 555 | 665 | 750 |
Types
- 60°C (140°F): TW, UF
- 75°C (167°F): RHW, THHW, THW, THWN, XHHW, USE, ZW
- 90°C (194°F): FEP, FEPB, MI, RHH, RHW-2, SA, SIS, TBS, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
Table 310.15(B)(17)
(formerly Table 310.17)
Allowable ampacities of single insulated copper conductors rated up to and including 2000 Volts in free air, based on ambient temperature of 30°C (86°F).
Size | Temperature Rating of Copper Conductor | ||
---|---|---|---|
(AWG or kcmil) | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) |
18 AWG | ā | ā | 18 |
16 AWG | ā | ā | 24 |
14 AWG* | 30 | 35 | |
12 AWG* | 35 | 40 | |
10 AWG* | 50 | 55 | |
8 AWG | 60 | 70 | 80 |
6 AWG | 80 | 95 | 105 |
4 AWG | 105 | 125 | 140 |
3 AWG | 120 | 145 | 165 |
2 AWG | 140 | 170 | 190 |
1 AWG | 165 | 195 | 220 |
1/0 AWG | 195 | 230 | 260 |
2/0 AWG | 225 | 265 | 300 |
3/0 AWG | 260 | 310 | 350 |
4/0 AWG | 300 | 360 | 405 |
250 KCMIL | 340 | 405 | 455 |
300 KCMIL | 375 | 445 | 500 |
350 KCMIL | 420 | 505 | 570 |
400 KCMIL | 455 | 545 | 615 |
500 KCMIL | 515 | 620 | 700 |
600 KCMIL | 575 | 690 | 780 |
700 KCMIL | 630 | 755 | 850 |
750 KCMIL | 655 | 785 | 885 |
800 KCMIL | 680 | 815 | 920 |
900 KCMIL | 730 | 870 | 980 |
1000 KCMIL | 780 | 935 | 1055 |
1250 KCMIL | 890 | 1065 | 1200 |
1500 KCMIL | 980 | 1175 | 1325 |
1750 KCMIL | 1070 | 1280 | 1445 |
2000 KCMIL | 1155 | 1385 | 1560 |
Types
- 60°C (140°F): TW, UF
- 75°C (167°F): RHW, THHW, THW, THWN, XHHW, ZW
- 90°C (194°F): FEP, FEPB, MI, RHH, RHW-2, SA, SIS, TBS, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
* Unless otherwise specifically permitted elsewhere in the NEC NFPA70 Code, the overcurrent protection for conductor types marked with an asterisk shall not exceed 15A for No. 14 copper, 20A for No. 12 copper, and 30A for No. 10 copper, after any correction factors for ambient temperature and number of conductors have been applied.
Table 310.15(B)(3)(a)
Adjustment factors for more than three current-carrying conductors in a raceway or cable.
Where the number of current-carrying conductors in a raceway or cable exceeds 3, the allowable ampacities shall be reduced per the table below.
Number of current-carrying conductors* | Percent of values in tables as adjusted for ambient temperature (if necessary) |
---|---|
4 - 6 | 80 |
7 - 9 | 70 |
10 - 20 | 50 |
21 - 30 | 45 |
31 - 40 | 40 |
41 and more | 35 |
* Does NOT include ground
Table 310.15(B)(2)(a)
Temperature Correction Factors
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor shown per the table below.
Ambient Temperature | 60°C (140°F) | 75°C (167°F) |
90°C (194°F) |
|
---|---|---|---|---|
50°F or less | 10°C or less | 1.29 | 1.20 | 1.15 |
51-59°F | 11 to 15°C | 1.22 | 1.15 | 1.12 |
60-68°F | 16 to 20°C | 1.15 | 1.11 | 1.08 |
69-77°F | 21 to 25°C | 1.08 | 1.05 | 1.04 |
78-86°F | 26 to 30°C | 1.00 | 1.00 | 1.00 |
87-95°F | 31 to 35°C | 0.91 | 0.94 | 0.96 |
96-104°F | 36 to 40°C | 0.82 | 0.88 | 0.91 |
105-113°F | 41 to 45°C | 0.71 | 0.82 | 0.87 |
114-122°F | 46-50°C | 0.58 | 0.75 | 0.82 |
123-131°F | 51-55°C | 0.41 | 0.67 | 0.76 |
132-140°F | 56-60°C | - | 0.58 | 0.71 |
141-149°F | 61-65°C | - | 0.47 | 0.65 |
150-158°F | 66-70°C | - | 0.33 | 0.58 |
159-167°F | 71-75°C | - | - | 0.50 |
168-176°F | 76-80°C | - | - | 0.41 |
177-185°F | 81-85°C | - | - | 0.29 |